| Region/District: | | | |
| Cabinet No.: | | | |
| Road No.: | LGA No.: | Job No.: | |
| Road name: | Suburb: | | |
| Operational Inspection | | | |
| Is the cabinet shell OK? | | | |
| Are all cabinet door locks functional? | | | |
| Are all door hinges OK? | | | |
| Is the cabinet labelled externally? | | | |
| Are the conduits entering the cabinet sealed? | | | |
| Is the cabinet chassis earthed via the electrical system earth link? | | | |
| Is there compliant electrical separation to communications equipment? | | | |
| Has RCD protection been removed from the circuits powering ITS equipment? | | | |
| Does the RCD on the socket outlet test OK? | | | |
| Are there appropriate surge protection devices installed? | | | |
| Is the surge protection operational? | | | |
| Are the thermostats set to 35oC? | | | |
| Do the fans come on when the thermostat is adjusted manually towards the minimum temperature? | | | |
| Are the door seals in good condition and creating a good seal? | | | |
| Is there any equipment that is not being used? If so remove it and record what it was in the action taken column | | | |
| ACTION - Vacuum inside cabinet | | | |
| ACTION - Clean/Replace filters | | | |
| ACTION - Remove any disused equipment | | | |