8Type-1 PTSS monitoring, reporting and fault requirements#
A Type-1 PTSS monitoring, reporting and fault requirements shall comply with the requirements specified below.
8.1Type-1 Faults#
In the event of a fault, the traffic controller shall be alerted on the HRC in use with a visual and audible alert indicating the PTSU where the fault occurred.
Alerts shall be providing for the following:
- low battery alarm, shall be active for at least 60 minutes and no more than 90 minutes before PTSU shuts down
- green or yellow aspect fault, and
- critical faults.
8.1.1Type-1 Critical faults#
When a critical fault occurs:
- a)the PTSS shall go to an all red display on all PTSUs, and
- b)the HRC shall be unable to operate the PTSS until a self-check has been performed on all PTSUs.
The time taken to reach an all-red display where the PTSUs are inoperable depends on the state of the PTSS prior to the fault:
- Any signal head is displaying green: PTSS all-red and inoperable within 5 seconds.
- Any signal head is displaying yellow: PTSS all-red inoperable within 5-x seconds, where x is the amount of time the unit was displaying yellow before the fault occurred.
- All signal heads are displaying red: PTSS inoperable within 1 second.
In addition to Items c, d, f, g, i and j listed under Section 2.8.2 of AS 4191, critical faults shall include the following:
- a)movement of the PTSU after installation, detected through:
- i.monitored GPS location (where a GPS is installed) of the PTSU exceeding the installed location by 30 m
- ii.monitored directional compass position of the PTSU exceeds installed position by +- 20° (yaw)
- iii.monitored inclination of the PTSU exceeds installed position by ± 20° (roll or pitch).
- b)loss of communication
- c)red aspect fault
- d)conflicting green signals occurring in shuttle control, and
- e)undefined behaviour or system crash.