B9Documentation of test results#
The presentation of the results shall specifically address the objectives of this Technical Specification as outlined in Clause 4, as well as providing the following:
- A record of all the temperature sensors and their time-stamped readings.
- The maximum internal temperature (TI) at each 30s interval, as well as the identifier of the sensor producing the maximum temperature reading.
- The average internal temperature at each 30s interval.
- The average ambient temperature (TA) at each 30s interval.
- The temperature difference between the cabinet and ambient temperature (ΔT) at each 30s interval.
- The difference between the maximum and minimum cabinet temperatures at each 30s interval.
- A plot of TI, TA and ΔT with time(s).
- The set-point of the thermostat used in testing.
- A diagrammatic layout which clearly shows the location of all the test sensors in the cabinet, test sources, cooling devices and air inlets.
- Details of the manufacturer and model of the test sensors and data logger.
- A clear, high resolution photo of:
- the test enclosure both before and after the test
- the location of all the test sensors in the cabinet, and
- the testing equipment including; test chamber, radiation and conduction heat sources, and data loggers.
Test results shall be presented using an electronic Microsoft Excel Spreadsheet template provided by the Director (ITS Technologies). A double-sided A4 hard copy of the test report and an electronic copy of the report and the populated excel spreadsheet template shall be provided to the Director (ITS Technologies) upon completion of testing.