5.8Specifying a residual current device#

When specifying the RCD, the following characteristics in Table 5 8(a) (with typical parameters) need to be considered and detailed for the particular application:

Table 5.8(a) – Typical residual current device characteristics
CharacteristicRCCBRCBO
Type of installationFixed installation, mobile installationFixed installation, mobile installation
Rated voltage (Un)240 / 415240 / 415
Rated frequency (Hz)5050
Rated making and breaking capacity (kA)3, 4.5, 6, 103, 4.5, 6, 10
Number of poles and current pathsSingle pole RCCB with two current paths Two pole RCCB Three pole RCCB Three pole RCCB with four current paths Four pole RCCBSingle pole RCBO with one overcurrent protected pole and uninterrupted neutral Two pole RCBO with one overcurrent protected pole Two pole RCBO with two overcurrent protected poles Three pole RCBO with three overcurrent protected poles Three pole RCBO with three overcurrent protected poles and uninterrupted neutral Four pole RCBO with three overcurrent protected poles Four pole RCBO with four overcurrent protected poles
Rated current (A) (In)6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100, 1256, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125
Overcurrent protectionWithout overcurrent protectionWith overcurrent protection
Tripping characteristic3In < B ≤ 5In 5In < C ≤ 10In 10In < D ≤ 20In
Rated residual operating current (mA)6, 10, 30, 100, 300, 5006, 10, 30, 100, 300, 500
Operating characteristicAC, AAC, A
Mounting methodDIN railDIN rail
Type of terminalsScrew typeScrew type

The following (Table 5.8(b)) is a typical specification example of a single phase 16 A / 30 mA RCD with overcurrent protection:

Table 5.8(b) – Typical residual current device specification
Type of installationFixed
Rated voltage (Un)240 V
Rated frequency50 Hz
Rated short-circuit capacity Icn6 kA
Number of poles and current pathsSingle pole
Overcurrent protectionRCBO
Rated current (In)16 A
Tripping characteristic (RCBO)Type C
Rated residual operating current (IΔn)30 mA
Operating characteristicsClass AC
Degree of protection (IP)Unenclosed
Method of mountingSwitchboard, DIN rail
Type of terminalsScrew-type
Source: TRUM Vol 4 Part 3 · pages 56–57 Open PDF at this page Search this document