6.18Summary#

6.18.1Power surge protection devices#

  • Determine if SPDs are required.
  • Provide primary line-to-neutral protection at installation entry.
  • Provide secondary line-to-neutral and neutral-to-earth protection at DB or equipment if required.
  • Select surge rating in accordance with table for location.
  • Ensure 10–20 m cable between primary and secondary protection.
  • Provide 32 A or 63 A SPD fuse.
  • Keep SPD cables short and straight.
  • Design good earthing and bonding.
  • Communications surge protection devices
  • Determine if SPDs are required.
  • Provide primary protection at installation entry close to MSB.
  • Provide secondary protection at equipment if required.
  • Refer communications equipment manufacturer for SPD recommendations.
  • Connect communications SPD earth and power SPD earth to common earth point.
  • Connect common earth point to electrical earth.
  • Keep SPD cables short and straight.
  • Design good earthing and bonding.