6.13Specifying power surge protection devices#

Before specifying SPDs, ensure that the products selected are from reputable manufacturers and are suitable for the application.

The following provides typical minimum specifications for power SPDs according to their location:

Table 6.13(a) – Typical specifications for category C3–C2 surge protection devices
Category C3–C2, high risk service entrance (MEN link) surge protection devices
Nominal voltage U n220–240 V ac
Maximum continuous operating voltage U cMax 275 V ac
Voltage protection level U pMax 850 V at 3 kA / 1200 V at 20 kA
Maximum surge current I max100 kA 8 / 20 µs
Nominal surge current I n40 kA 8 / 20 µs per mode
Protection modesSingle mode (L1-N, L2-N, L3-N)
EnclosureTo suit application
Mounting35 mm DIN rail / to suit application
Terminals≤25 mm² stranded power cable ≥1.5 mm² stranded remote indication
Status indicationVisual, voltage free contact for remote indication
MOV moduleNone / Replaceable
Table 6.13(b) – Typical specifications for Category C1-B surge protection devices
Category C1-B, service entrance, sub distribution board surge protection devices
Nominal voltage U n220–240 V ac
Maximum continuous operating voltage U cMax 275 V ac
Voltage protection level U pMax 850 V at 3 kA / 1200 V at 20 kA
Maximum surge current I max40 kA 8 / 20 µs
Nominal surge current I n20 kA 8 / 20 µs per mode
Protection modesSingle mode with MEN link (L1-N, L2-N, L3-N) Single mode no MEN link (L1-N, L2-N, L3-N, N-E)
EnclosureTo suit application
Mounting35 mm DIN rail / to suit application
Terminals≤25mm² stranded power cable ≥1.5mm² stranded remote indication
Status indicationVisual, voltage free contact for remote indication
MOV moduleNone / Replaceable
Table 6.13(c) – Typical specifications for Category A surge protection devices
Category A, sub-circuit surge protection devices
Nominal voltage U n220–240 V ac
Maximum continuous operating voltage U cMax 275 V ac
Voltage protection level U pMax 850 V at 3 kA – electrical equipment Max 600 V at 3 kA – electronic equipment
Maximum surge current I max15 kA 8 / 20 µs
Nominal surge current I n8 kA 8 / 20 µs per mode
Protection modesL-N, L-E, N-E
EnclosureTo suit application
Mounting35 mm DIN rail / to suit application
Terminals≤10mm² stranded power cable ≥1.5mm² stranded remote indication
Status indicationVisual, voltage free contact for remote indication
MOV moduleNone / Replaceable
Table 6.13(d) – Typical specifications for Category A surge reduction filters
Category A, sub-circuit surge reduction filters
Nominal voltage U n220–240 V ac
Maximum continuous operating voltage U cMax 275 V ac
Voltage protection level U pMax 600 V at 3 kA – electronic equipment
Maximum surge current I max10 kA 8 / 20 µs
Nominal surge current I n5 kA 8 / 20 µs per mode
Protection modesL-N, L-E, N-E
dv / dt<50 V / uS at 20 kA (8 / 20 uS)
EnclosureTo suit application
Mounting35 mm DIN rail / to suit application
Terminals≤10mm² stranded power cable ≥1.5mm² stranded remote indication
Status indicationVisual, voltage free contact for remote indication

The important parameters when selecting power SPDs are:

  • Imax: The maximum 8 / 20 µs surge current between any one phase and neutral that the SPD can withstand for a single strike
  • In: The 8 / 20 µs surge current the SPD can withstand for 15 strikes
  • Up: Voltage protection level, the residual voltage after the surge has passed the SPD, and
  • shunt or series connection.

Shunt – typically primary protection and some secondary applications:

  • connected across L to N or L to E
  • length of connection leads affects let-through voltage, and
  • load current does not determine size of SPD.

Series – typically secondary protection:

  • connected in circuit
  • shunt connection is internal, eliminating effects of lead length, and
  • load current is a factor in determining SPD.
Source: TRUM Vol 4 Part 3 · pages 89–92 Open PDF at this page Search this document